HOME DIMENSIONS

Doors, hallways, ceilings and sockets:
standard home dimensions

An 83 cm door, a 90 cm hallway, 2.50 m ceilings, sockets at least 5 cm off the floor: where these figures come from, which ones are mandatory in France and which are just custom. Plus two calculations to check a room.

Sockets and ceiling height: check a room

How many sockets the French wiring standard requires in a room, and whether your ceiling height clears the legal thresholds.

Room
24 m²
switches 0.90 – 1.30socket1.30 m5 cm
Minimum sockets
6
One socket per 4 m² started, at least five (seven above 28 m²).
Socket height
centre 5 cm up at least
From the finished floor, for a 16 A socket; 12 cm for a 32 A cooker socket. In new accessible French housing: 1.30 m at most, with one socket per room allowed higher.

Interior door dimensions

A standard interior door set has a leaf 204 cm high and 63, 73, 83 or 93 cm wide. The actual clear passage is about 3 cm narrower, because of the frame, and the opening to leave in the partition about 7 cm wider: an 83 cm door set gives a clear passage of about 80 cm and needs a rough opening of about 90 × 207 cm. These differences vary from one manufacturer to another: the technical data sheet is what counts.

In new housing in France, the accessibility rule sets the minimum: a nominal width of 0.80 m for interior doors (0.77 m of clear passage) and 0.90 m for the front door (0.83 m of clear passage), with a step of 2 cm at most.

Common interior door dimensions
LeafClear passage, approx.Rough opening, approx.Typical use
63 × 204 cm60 cm70 × 207 cmToilet, cupboard, older homes
73 × 204 cm70 cm80 × 207 cmBedroom, bathroom, older homes
83 × 204 cm80 cm90 × 207 cmNew-build standard, accessible
93 × 204 cm90 cm100 × 207 cmFront door, wide passage

Hallway width

In new housing in France, interior circulation areas are at least 0.90 m wide: that’s the accessibility rule for every building permit applied for since April 2016. In older homes, you often come across 80 cm, or even less.

At 90 cm you can get through, but turning into a side door is tight; at 1 m, you can pass someone if one of you steps aside; at 1.20 m, you can put a shoe cabinet or a console table there without getting in the way. In front of a door, accessible housing requires a clear space 1.20 m wide, 1.70 m deep on the side where you push the door and 2.20 m on the side where you pull it.

  • 0.90 m: the minimum in new homes in France
  • 1.00 m: two people can pass
  • 1.20 m: room for a shallow piece of furniture

Ceiling height

Contrary to a widespread belief, no national text in France requires 2.50 m ceilings in new builds: the building code sets no minimum height. The 2.50 m found in most recent homes is a builders’ custom.

What does exist: under French decency rules, the main room of a home has 9 m² with a 2.20 m ceiling height, or 20 m³; the standard French départemental health regulations require 2.20 m, and some départements 2.30 or 2.50 m. A 2023 decree had made 2.20 m a national rule: the Conseil d’État struck it down on that point in 2024, so the départemental regulations remain the reference. Finally, below 1.80 m, the area counts neither towards the habitable floor area nor towards the Carrez law area.

Ceiling height thresholds
HeightWhat it triggersLegal reference
1.80 mBelow it, the area doesn’t count (habitable floor area, Carrez law)Building code (CCH), art. R. 156-1; Decree 67-223, art. 4-1
2.20 m, decent homeMinimum for the main room of a decent home (or 20 m³)Decree 2002-120, art. 4
2.20 m, health regulationsMinimum in the standard health regulations (2.30 or 2.50 m in some départements)Départemental health regulations, art. 40.4
2.50 mCommon practice in new builds, not a requirement—

Electrical socket height

NF C 15-100, the French wiring standard, sets a minimum height, not an ideal one: the middle of a 16 A socket is at least 5 cm above the finished floor, that of a 32 A socket (for a cooker) at least 12 cm. Sockets fitted around 25 or 30 cm are placed there out of habit. In the kitchen, worktop sockets are at least 5 cm above the worktop, and never above the sink or the hob.

In new accessible housing in France, switches and other controls are between 0.90 and 1.30 m from the floor, and sockets at 1.30 m at most, though one socket per room may be higher.

Socket and switch heights
ItemHeightLegal reference
16 A socketMiddle at least 5 cm above the finished floorNF C 15-100
32 A socket (cooker)Middle at least 12 cm above the floorNF C 15-100
Kitchen socketAt least 5 cm above the worktopNF C 15-100
Switch, new accessible housingBetween 0.90 and 1.30 mOrder of 24 December 2015, art. 11
Socket, new accessible housing1.30 m at most (one per room may be higher)Order of 24 December 2015, art. 11

How many sockets per room?

NF C 15-100 sets a minimum number of sockets per room, to be met in new builds and when the whole electrical installation is renovated. The tool works it out for the area of your room.

Minimum number of sockets per room under NF C 15-100
RoomMinimum
Living room1 per 4 m², at least 5 (7 above 28 m²)
Bedroom3
Kitchen6, including 4 above the worktop (3 if 4 m² or less)
Bathroom1, outside the safety zones
Entrance or hallway over 4 m²1
Other room over 4 m²1
Separate toiletNone required

Sources

FREQUENTLY ASKED QUESTIONS

Doors, hallways, ceilings, sockets

What is the standard width of an interior door?
An 83 cm leaf in new builds, which gives a clear passage of about 80 cm; 63, 73 and 93 cm also exist. The standard height is 204 cm. In new housing in France, the minimum nominal width is 0.80 m (0.77 m of clear passage).
What are the dimensions of a front door?
A nominal width of 90 cm in new housing in France, which gives at least 0.83 m of clear passage, with a threshold of 2 cm at most. 80 cm front doors are found in older homes.
What is the minimum width of a hallway?
0.90 m in new housing in France, an accessibility rule for building permits applied for since April 2016. There’s no minimum in older homes; 1 m lets two people pass.
What is the minimum ceiling height?
No height is required at national level in France to build. To rent a home out, its main room must have a 2.20 m ceiling height with 9 m², or 20 m³; your département’s health regulations may require 2.20, 2.30 or 2.50 m. Below 1.80 m, the area doesn’t count.
How high should an electrical socket be?
With its middle at least 5 cm above the finished floor (12 cm for a 32 A socket), under NF C 15-100, the French wiring standard. Above that, the height is up to you, except in new housing, where sockets stay at 1.30 m at most.
How many sockets in a 30 m² living room?
At least 8: one per 4 m², with a minimum of 7 above 28 m².

Put these dimensions on your plan

Draw the walls, place the doors at their real width, check the hallways: a plan to scale tells you straight away what fits.

Draw my home to scale